=== 6.6.1 Studs to raking beams ===
 
=== 6.6.1 Studs to raking beams ===
The quantity or spacing of shear studs that are required to be welded to each of the beams in a steel frame for a composite slab, are typically specified by the structural engineer. These are noted in a variety of ways on the engineers beam layout general arrangement drawings, but most commonly by a note next to each beam indication the quantity of shear studs for that beam, or the spacing between the of studs along the beam. When SMD add the shear stud labels to our drawings, we work to the information from the engineer’s drawings.
+
The quantity or spacing of shear studs required on composite steel beams are specified by the steel designer. This is typically the structural engineer with the quantity or spacing of studs indicated as a note against each individual beam on the steel general arrangement drawing. SMD, where contracted, add shear stud labels to the deck general arrangement drawings using the information specified by the steel designer.
  
For example, with SMD TR60+ profile, the deck troughs fall at 333mm centres. The studs must be installed in the troughs, so to beams perpendicular to the deck span, the studs could be specified at 333mm centres (i.e. 1 per trough). The quantity of studs would therefore be approximately the length of the beam divided by 333mm.
+
It is important where steel beams are raking across the deck span to consider the impact this has on stud numbers or spacings achievable due to the increase in the distance between troughs caused by the angle of the rake. Some steel frame design software packages only consider stud numbers in relation to beam length and requirement for the composite beam design without considering a raking deck orientation or whether it is possible to get the studs onto the beam where the deck is raking.  Detailed below are examples where this issue needs consideration.
  
  
 
'''Studs at 333mm centres to beam perpendicular to deck span'''  
 
'''Studs at 333mm centres to beam perpendicular to deck span'''  
  
One issue that often arises is that no consideration has been made to beams that are raking to the decking span.
+
SMD TR60+ profile has deck troughs at 333mm, meaning where deck is perpendicular to the beam CL, studs must be detailed at 333mm. The quantity of studs achievable in this situation is essentially beam length divided by 333.  This can be increased by detailing paris per trough if the beam width permits
 
+
  
 
[[File:6.6.1a-V10.5.jpg|500px|link=]]
 
[[File:6.6.1a-V10.5.jpg|500px|link=]]
  
 
If the engineer or the related design software just calculates studs based on the beam length and the spacing, it will not calculate correctly for beams that are raking to the deck span.
 
  
  
'''Studs at 333mm centres perpendicular to the beam'''
+
'''Studs at 333mm centres along the raking beam'''
  
The dotted centre lines show the location of the deck troughs and therefore where the shear studs must be located on the beam.
+
The dotted centre lines show the location of the deck troughs and therefore where the shear studs must be located on the beam.  
  
  
Line 59: Line 56:
 
Trying to instal 11 studs at 333mm centres in line with the angle of the beam is not possible (studs shown red where they cannot be installed).
 
Trying to instal 11 studs at 333mm centres in line with the angle of the beam is not possible (studs shown red where they cannot be installed).
  
In the example shown and due to the angle of the beam, the deck troughs effectively fall at 213mm centres perpendicular to span and not in the deck troughs.  
+
In the example shown and due to the angle of the beam, the studs effectively fall at 213mm centres perpendicular to span which is not in the deck troughs and, hence, not achievable.
  
  
 
'''Studs at 333mm centres perpendicular to the deck (not the beam)'''
 
'''Studs at 333mm centres perpendicular to the deck (not the beam)'''
  
Placing shear studs on the centre line of the deck troughs and in line with the raking beams, means the studs are actually located 521mm apart (and not 333mm in relation to the angle of the beam).
+
Placing shear studs on the centre line of the deck troughs and in line with the raking beams, means the studs are actually located 521mm apart (and not 333mm due to the angle of the beam).
  
  
Line 70: Line 67:
  
  
If it is essential to achieve the quantity of studs on the beam, and the beam flanges are wide enough, studs in pairs will be installed at each end of the beam until the correct number of studs have been installed.  
+
If it is essential to achieve the quantity of studs on the beam, and the beam flanges are wide enough, studs in pairs can be installed at each end of the beam to achieve the correct number of studs. This will need to be checked by the steel beam designer as each stud in a pair  provides a lower resistance than a single stud.  Therefore, the number may need to be increased for this configuration.  
  
  
'''Stud number and spacing consideration'''s
+
'''Stud number and spacing considerations'''
  
 
Consideration should be made when specifying the shear stud quantity/spacing on a steel frame that has beams that are raking to deck span.
 
Consideration should be made when specifying the shear stud quantity/spacing on a steel frame that has beams that are raking to deck span.
  
Particular attention should be made on raking beams with narrow beam flanges as it may be impossible to double up studs (in pairs) at each end of the beam due to the flange width (shear studs require a minimum of 76mm gap between each stud when placed in pairs - see Fig.6.6c and Fig.6.6f).
+
In summary, it is important to consider raking beams and influence on number/spacings when specifying shear studs on beams that are not perpendicular or parallel to the deck span. Particular attention should be made on raking beams with narrow top flanges as it may be impossible to double up studs (in pairs) due to the flange width. Where beams are wider it may be possible to separate the deck along the CL of beam with closure flashings to enable studs to be installed - contact SMD Technical team for further guidance.  
  
  

Revision as of 14:59, 25 March 2022

In accordance with BS EN 1994-1-1 or BS5950-3 Section 3.1:1990+A1 2010, the dimensions and configurations shown in Figs 6.6a to 6.6f must be followed to ensure the welded shear studs are effective to provide the documented stud resistance values.


6.6a.png

Refer SMD Detail Sheet SMD.DOD.185 - R51 Single studs


6.6b.png

Refer SMD Detail Sheet SMD.DOD.183 - R51 Staggered studs


6.6c.png

Refer SMD Detail Sheet SMD.DOD.184 - R51 Studs in pairs


6.6d.png

Refer SMD Detail Sheet SMD.DOD.182 - TR+ Single studs


6.6e.png

Refer SMD Detail Sheet SMD.DOD.180 - TR+ Staggered studs


6.6f.png

Refer SMD Detail Sheet SMD.DOD.181 - TR+ Studs in pairs


6.6.1 Studs to raking beams

The quantity or spacing of shear studs required on composite steel beams are specified by the steel designer. This is typically the structural engineer with the quantity or spacing of studs indicated as a note against each individual beam on the steel general arrangement drawing. SMD, where contracted, add shear stud labels to the deck general arrangement drawings using the information specified by the steel designer.

It is important where steel beams are raking across the deck span to consider the impact this has on stud numbers or spacings achievable due to the increase in the distance between troughs caused by the angle of the rake. Some steel frame design software packages only consider stud numbers in relation to beam length and requirement for the composite beam design without considering a raking deck orientation or whether it is possible to get the studs onto the beam where the deck is raking. Detailed below are examples where this issue needs consideration.


Studs at 333mm centres to beam perpendicular to deck span

SMD TR60+ profile has deck troughs at 333mm, meaning where deck is perpendicular to the beam CL, studs must be detailed at 333mm. The quantity of studs achievable in this situation is essentially beam length divided by 333. This can be increased by detailing paris per trough if the beam width permits

6.6.1a-V10.5.jpg


Studs at 333mm centres along the raking beam

The dotted centre lines show the location of the deck troughs and therefore where the shear studs must be located on the beam.


6.6.1b-V10.5.jpg


Trying to instal 11 studs at 333mm centres in line with the angle of the beam is not possible (studs shown red where they cannot be installed).

In the example shown and due to the angle of the beam, the studs effectively fall at 213mm centres perpendicular to span which is not in the deck troughs and, hence, not achievable.


Studs at 333mm centres perpendicular to the deck (not the beam)

Placing shear studs on the centre line of the deck troughs and in line with the raking beams, means the studs are actually located 521mm apart (and not 333mm due to the angle of the beam).


6.6.1c-V10.5.jpg


If it is essential to achieve the quantity of studs on the beam, and the beam flanges are wide enough, studs in pairs can be installed at each end of the beam to achieve the correct number of studs. This will need to be checked by the steel beam designer as each stud in a pair provides a lower resistance than a single stud. Therefore, the number may need to be increased for this configuration.


Stud number and spacing considerations

Consideration should be made when specifying the shear stud quantity/spacing on a steel frame that has beams that are raking to deck span.

In summary, it is important to consider raking beams and influence on number/spacings when specifying shear studs on beams that are not perpendicular or parallel to the deck span. Particular attention should be made on raking beams with narrow top flanges as it may be impossible to double up studs (in pairs) due to the flange width. Where beams are wider it may be possible to separate the deck along the CL of beam with closure flashings to enable studs to be installed - contact SMD Technical team for further guidance.


6.6.1d-V10.5.jpg