− | The maximum span values in Table 8.1a are based on the following design criteria: | + | The maximum span values in [[file:8.1.jpg|Table 8.1a]] are based on the following design criteria: |
− | + | *Imposed Load of 1.5kN/m² or Line Load of 2kN/m | |
− | + | *Partial Load Factor of 1.5 (considering all loads as ‘Variable’) | |
− | + | *Imposed Load Deflection Limit of Span/200 | |
− | + | *Wind Uplift of 1.5kN/m², subject to appropriate fixings | |
− | + | *Wind Uplift Deflection Limit of Span/90 | |
− | For more detailed designs, refer to '''[https://smdltd.co.uk/technical/elements-design-software/ SMD | + | For more detailed designs, refer to '''[https://smdltd.co.uk/technical/elements-design-software/ SMD Elements® design software version 2.0]''' for more information |
'''[https://smdltd.co.uk/products-services/roof-deck/ More extensive load tables can be found on the SR product-specific data sheets]''' | '''[https://smdltd.co.uk/products-services/roof-deck/ More extensive load tables can be found on the SR product-specific data sheets]''' |
Revision as of 16:22, 2 February 2017
Back to main Contents page
The maximum span values in Table 8.1a are based on the following design criteria:
- Imposed Load of 1.5kN/m² or Line Load of 2kN/m
- Partial Load Factor of 1.5 (considering all loads as ‘Variable’)
- Imposed Load Deflection Limit of Span/200
- Wind Uplift of 1.5kN/m², subject to appropriate fixings
- Wind Uplift Deflection Limit of Span/90
For more detailed designs, refer to SMD Elements® design software version 2.0 for more information
More extensive load tables can be found on the SR product-specific data sheets
Other items within 8.0 - Design - Roof deck:-
- 8.0 - Design - Roof deck
- 8.1 - Quality
- 8.2 - Spans
- 8.3 - Loads
- 8.4 - Standard end laps
- 8.5 - Extended end laps
- 8.6 - Raking supports and cutting
- 8.7 - Cantilevers
- 8.8 - Sheet lengths
- 8.9 - Fire rating
- 8.10 - Durability
- 8.11 - Acoustics
- 8.12 - Airtightness
- 8.13 - Fixing specification
- 8.14 - Non-fragility
- 8.15 - Diaphragm design
- 8.16 - Protex® warranted insulated system
- 8.17 - Aesthetics